4.4.7.2.3 Cold temperature. Continuing with the same assembly, the pressure
shall be observed and then the assembly shall be placed in a cold chamber at
-4O° ± 2°F (-4O ± 2°C) for 2 hours. A check shall be made for leakage of the
testing fuel. The pressure jig shall then be removed from the chamber and
allowed to remain at 77º± 2ºF (25º±.6ºC) for 3 hours. If a pressure drop to 20
psi (.138 MPa) or less on the gage is observed, the test shall be considered
a failure.
Type I 2 inch Bung
Type I - .75 inch Vent
FIGURE 1.
TYPE 1 GASKETS.